Modem functions – E-Mon Energy Software User Manual

Page 209

Advertising
background image

Status Bar Function Codes and Error Flag Codes

tE-Mon Energy User Manual

B-2

E-MON

18

0

Error: No connection

Lost connection before command was

complete.

19

0

Error: Time out

Did not get the proper response from

Hardware in the specified time.

20

0

Invalid cmd

An unknown command was sent to the

Hardware or security level not allowing it.

21

0

Re-download

For high resolution meter, the profile data

exceeds the max pulse limit. The day block

will be re-downloaded one more time.

22

0

Err: data over limit

At least one of the interval data exceeds the

rated pulse. Check the Meter configuration in

the database, especially the Pulse Factor.

23

0

Err: missing day block

At least one day block of interval profile data

is missing during download. The download

date will be updated.

24

0

Err: data length

The profile data block has the wrong length.

Software keeps downloading but it won’t

update the download date.

25

0

Error: recr param

During download, cannot get the recorder

parameter from database, download failed.

26

0

Error: database update

When sending Recorder or Meter information,

failed to update the database with the

information sent. Or when download failed to

update the profile to the database.

27

0

New Location! Click [Add Location] button

to setup

When a remote recorder calls-in, E-Mon

Energy™ will query the group/location from

the device, if E-Mon Energy can not find it in

the database, it will prompt you to add a

location.

28

3

STANDBY

E-Mon Energy is waiting to receive in-coming

calls (AMR). Or Access location is ready to

make the connection.

29

3 Err

or

Refer to status bar panel 0 for the cause.

Modem Functions

No

Status Loc

Status Code

Description

1

0

Modem Init Error

Transmission Modem will not dial out.

2

0

Auto Answer READY

E-Mon Energy is waiting to receive in-coming

calls (AMR).

3

0

Error in Auto Answer setup

Failed to set the modem to “not waiting” ring.

4

0

Set Dial-Timeout Error

Modem return error when sending the modem

dial timeout command.

5

0

Modem Init Timeout

Modem timeout when sending the init string

to Modem.

6

0

Bad data

Data is Corrupted.

7

0

Unexpected Data

Data Received has wrong Check Sum.

8

0

Auto Answer completed at (time stamp)

Bye command sent to Hardware .

9

0

Auto Answer terminated at (time stamp)

Other disconnection than sending Bye

command.

10

0

Auto Answer line dropped at (time stamp)

Line disconnected when neither hardware nor

software initiates the disconnection.

11

0

Register comport status’

Auto-answer synchronizes the comport status

with modem.

12

3

Initialize Modem…

Sending initialization and configuration

Advertising