3.4 Fieldbus

Type
Address Map

109

(ON = Applicable bit is “1”, OFF = Applicable bit is “0”)

Signal Type

Bit

Symbol

Contents

Details

Current

Position

32

Bit

data

32-bit signed integer indicating the current position

Unit: 0.01mm

(Example) If +10.23mm, input 000003FF

H

(1023mm in

decimal system).

(Note) Negative numbers are two’s implement.

3.7 (28)

Command

Current

32

Bit

data

32-bit integer

The electrical current presently specified by a command

is indicated.

The setting unit is mA.

This resistor makes an output in hexadecimal numbers.

(Example) Reading: 000003FF

H

=1023 (Decimal number)

=1023mA

3.7 (28)

Current

Speed

16

Bit

data

32-bit integer

The current speed is indicated.

Unit: 1.0mm/sec or 0.1mm/sec.

A change of the unit is to be conducted on Gateway

Parameter Setting Tool.

(Example) Reading: 000003FF

H

=1023 (Decimal number)

= 10.23mm/sec

(Note) Negative numbers are two’s implement.

3.7 (28)

Alarm

Code

16

Bit

data

16-bit integer

The simple alarm code [Refer to Chapter 8

Troubleshooting] is output while an alarm is issued

(ALM of Status Signal is ON).

3.7 (28)

b15

EMGS This signal turns ON during an emergency stop

3.7 (2)

b14

CRDY This signal turns ON when the controller is standing by.

3.7 (1)

b13

ZONE2 “ON” for the current position within the zone set range

The zone range setting is necessary for the parameter.

b12

ZONE1 “ON” for the current position within the zone set range

The zone range setting is necessary for the parameter.

3.7 (11)

b11

b10

b9

Unavailable

b8

MEND

This signal turns ON when movement command is

complete, stopping with servo-on and pressing is

missed, and turns OFF when in emergency stop with

servo is OFF and while CSTR Signal is ON

3.7 (21)

b7

BALM Warning for absolute battery voltage drop

This signal turns ON with battery voltage drop

3.7 (22)

b6

Unavailable

b5

PSFL

This signal turns ON when the actuator missed the load

in push-motion operation.

3.7 (20)

b4

SV

This signal turns ON when operation standby is

complete (Servo is ON).

3.7 (5)

b3

ALM

This signal is ON while an alarm is generated.

3.7 (3)

b2

MOVE This signal is ON while in movement.

3.7 (8)

b1

HEND

This signal turns ON at home return complete and is

kept unless the home position is lost due to a fact such

as an alarm.

3.7 (6)

P

LC

In

pu

t

Status

Signal

b0

PEND

This signal turns ON when positioning is complete and

stopping with servo-on, and turns OFF when pressing is

missed and while CSTR Signal is ON

3.7 (9)