3.4 Fieldbus

Type

Address Map

114

(3) I/O signal assignment

(ON = Applicable bit is “1”, OFF = Applicable bit is “0”)

Signal Type

Bit

Symbol

Contents

Details

Target Position

32

Bit

data

32-bit signed integer indicating the current position

Unit: 0.01mm

Available range for Setting: -999999 to 999999

Set the target position with the value from the home

position.

(Example) If +25.40mm, input 000009EC

H

(2540 in

decimal system).

(Note) Input the negative value using a compliment of

2.

3.7 (28)

Positioning Width

32

Bit

data

32-bit integer

Unit: 0.01mm

Available range for Setting: 0 to 999999

(Example) If +25.40mm, input 000009EC

H

(2540 in

decimal system).

This register value has two meanings depending on the

operation type.

1) Positioning operation Ÿ

Range for positioning complete against the target

position

2) Pressing operation Ÿ

Pressing width (Pressing operation distance)

A pressing operation is performed when PUSH Signal

in the control signals is ON.

3.7 (28)

Command Speed

16

Bit

data

16-bit integer

Unit: 1.0mm/sec or 0.1mm/sec (It is set to 1.0mm/sec

in the initial setting.)

A change of the unit is to be conducted on Gateway

Parameter Setting Tool.

Available range for Setting: 1 to 65535

Specify the speed at which to move the actuator.

(Example) If 254.0mm/sec (1.0mm/s unit), input 09EC

H

(2540 in decimal system).

It may cause an alarm or a malfunction if executing a

movement command with 0 or a value more than the

maximum speed of the actuator.

3.7 (28)

Acceleration/Deceleration

16

Bit

data

16-bit integer

Unit: 0.01G

Available range for Setting: 1 to 300

Specify the speed at which to move the actuator. The

acceleration and deceleration will be the same value.

(Example) If 0.30G, input 001E

H

(30 in decimal system).

It may cause an alarm or a malfunction if executing a

movement command with 0 or a value exceeding the

maximum acceleration/deceleration of the actuator.

3.7 (28)

P

LC

O

ut

pu

t

Pressing Current Limit

16

Bit

data

16-bit integer

Unit : %

Available range for Setting: 0 to 100

Indicate the current value for pressing operation.

(Example) If “50%”, input “007F

H

”.

The pressing range available for indication differs

depending on the actuator (Refer to the catalog or

instruction manual for the actuator). It may cause an

alarm or a malfunction if executing a movement

command with a value more than the maximum

pressing current.

3.7 (28)