8] field network circuit (for field network type), Chapter 2 wiring, 2) cc-link type – IAI America MSCON User Manual

Page 52: 3) profibus-dp type

Advertising
background image

Chapter 2 Wiring

44

[8] Field Network Circuit (For Field Network Type)

Refer to the instruction manual of the master unit for each field network and constructed PLC

for the details of the circuit.



1) DeviceNet Type

MSCON

DeviceNet Type

V+

Drain

(Shield)

CAN_H

CAN_L

V-

RD

WT

BL

BK

RD

WT

BL

BK

V+

Drain

(Shield)

CAN_H

CAN_L

V+

Drain

(Shield)

CAN_H

CAN_L

V-

RD

WT

BL

BK

Communication power needs to be

supplied by an external device.

Connect the terminal resistor if the unit is

placed at the end of the network.

V-

Terminal Resistance

121Ω

Terminal Resistance

121Ω

24V

Power Supply

Class D grounding

(Formerly Class-III grounding : Grounding resistance at 100Ω or less)

Master Unit

Slave Device

2) CC-Link Type

MSCON

CC-Link Type

SLD and FG are internally connected.

Connect the terminal resistor if the unit is

placed at the end of the network.

The terminal resistor differs depending on the type

of the dedicated cable for CC-Link.
• Cable FANC-SBH··· 130Ω1/2W

(High Performance Cable

dedicated for CC-Link)

• Cable FANC-SB······ 110Ω1/2W

(CC-Link Dedicated Cable)

Class D grounding

(Formerly Class-III grounding:

Grounding resistance at 100Ω or less)

Master Unit

Slave Device

Terminal

Resistance

Terminal

Resistance

3) PROFIBUS-DP Type

MSCON

PROFIBUS Type

Terminal Resistance is required

to be mounted on the terminal.

Master Unit

Slave Device

Class D grounding

(Formerly Class-III grounding : Grounding resistance at 100Ω or less)