3.4 Fieldbus

Type

Address Map

80

3.4.2 Example for Address Map Construction for each Field Network

Shown below is an example for the address map by the combination of operation modes for

each Fieldnetwork. Refer to it for the address assignment.

The example for the address map shown below is provided for each field network, however is

described together for the networks of the same address assignment.

Note In the order of each field network address map description

1) DeviceNet and CompoNet

2) CC-Link

3) PROFIBUS, EtherNet/IP, MECHATROLINK, EtherCAT

٧

In the case of CC-Link

Station Type: Ver.2 Remote device station

Extended Cyclic Setting/Occupied Station Number Setting:

Register the information of the occupations displayed on Gateway Parameter Setting Tool to

the master unit. Connection cannot be established if information other than occupation is set.

[Refer to 3.2 Initial Setting.]

Caution: Ɣ Remote I/O Mode is selected, all the axes connected to MSCON are involved in

Remote I/O Mode.

Ɣ Only Positioner 3 Mode and Remote I/O Mode are available to be selected in

MECHATROLINK and CompoNet. (CompoNet occupies 32 bytes no matter of the

number of axes.)

[1] Address Map with Combination of Positioner 1/Simple Direct Modes and

Direct Indication Mode

3 types of examples are shown below for the contraction of the address maps when operation

is made with the combination of Simple Direct Mode and Direct Indication Mode for six axes for

each field network.

Example of

Combinations

Number of Simple Direct

Mode Axes

Number of Direct Indication

Mode Axes

1

6

0

2

4

2

3

0

6

1) DeviceNet (CompoNet is not applicable for this mode)

[Combination Example 1] When number of Simple Direct Mode axes is 6 and number of Direct

Indication Mode 0

(n is the top channel number for each PLC input and output between

MSCON and PLC)

PLCĺMSCON

MSCONĺPLC

CH No.

Contents

CH No.

Contents

n to n+1

Gateway Control

n to n+1

Gateway Status

n+2 to n+7

Demand

Command

n+2 to n+7

Response

Command

n+8 to n+11

Axis No.0 Control

Information

n+8 to n+11

Axis No.0 Status

Information

n+12 to n+15

Axis No.1 Control

Information

n+12 to n+15

Axis No.1 Status

Information

n+16 to n+19

Axis No.2 Control

Information

n+16 to n+19

Axis No.2 Status

Information

n+20 to n+23

Axis No.3 Control

Information

n+20 to n+23

Axis No.3 Status

Information

n+24 to n+27

Axis No.4 Control

Information

n+24 to n+27

Axis No.4 Status

Information

n+28 to n+31

Axis No.5 Control

Information

n+28 to n+31

Axis No.5 Status

Information

Advertising