Chapter 7 Parameter

261

[19] PIO jog velocity (Parameter No.26), PIO jog velocity 2 (Parameter No.47)

No.

Name

Symbol

Unit

Input Range

Default factory

setting

26 PIO Jog Velocity

IOJV

mm/s

[deg/s]

1 to Actuator’s

max. speed

100

This is the setting for the JOG operation velocity with JOG+/- Signal (JOG Input Command)

when PIO Pattern = 1 (Teaching Mode) is being selected.

Set an appropriate value in Parameter No.26 in accordance with the purpose of use.

Note 1: The maximum speed is limited to 250mm/s.

[20] Movement command type (Parameter No.27)

No.

Name

Symbol

Unit

Input Range

Default factory

setting

27 Movement Command Type

FPIO

-

0 : Level

1 : Edge

0

Set the input methods for the start signal (ST0 to ST6, or ST0 to ST2 if PIO Pattern = 5) when

PIO Pattern 4 = Solenoid Valve Mode 1 (7-point type) and PIO Pattern 5 = Solenoid Valve

Mode 2 (3-point type).

Set Value Input Method

Description

0

Level

The actuator starts moving when the input signal turns ON.

When the signal turns OFF during movement, the actuator will

decelerate to a stop and complete its operation.

1

Edge

The actuator starts moving when the rising edge of the input signal

is detected. The actuator will not stop when the signal turns OFF

during the movement, until the target position is reached.

[Level System]

[Edge System]

Move command input (ST0 to ST6)

Movement complete (PE0 to PE6)

Actuator movement

Target Position

Stop

Move command input (ST0 to ST6)

Movement complete (PE0 to PE6)

Actuator movement

Target Position