(26) Operation for Direct Indication Mode

It is operated with the data set in the PLC's target position register, positioning width register,

setup speed register, acceleration/deceleration register and pressing current limit setup

register.

Ɣ Example of operation (Pressing operation)

(Preparation) Set the axis numbers to be used in Direct Indication Mode with Gateway

Parameter Setting Tool.

1) Set the target position data in the target position register.

2) Set the positioning width (pressing width) data in the positioning width register.

3) Set the speed data to the speed register.

4) Set the acceleration/deceleration data to the acceleration/deceleration register.

5) Set the pressing current limit data in the pressing current limit value register.

6) Turn ON the pressing setup (PUSH) signal.

7) Specify the pressing direction using the pressing direction setup (DIR) signal.

8) In the condition where the positioning completion (PEND) signal is turned ON or under

movement signal (MOVE) is turned OFF, turn ON the positioning start (CSTR) signal.

The data items set in Steps 1) through 5) are read in the controller at the startup (ON edge)

of the CSTR signal.

9) After the CSTR signal is turned ON, the PEND signal is turned OFF after tpdf.

10) After confirming that the PEND signal is turned OFF or MOVE signal is turned ON, turn OFF

the CSTR signal. Do not change any value in each register until the CSTR signal has been

turned OFF.

11) The current position data is continuously updated.

12) When the CSTR signal is turned OFF and the motor current reaches the current limit value

set in Step 5), the PEND signal is turned ON. (Pressing complete)

Even when the positioning width (pressing width) set in Step 2) is reached, in the case that

the current does not reach the motor current limit value set in Step 5), the pressing and a

miss (PSFL) signal is turned ON. In this case, the PEND signal is not turned ON. (Pressing

and a miss)

13) After the PEND signal or PSFL signal is turned ON, turn OFF the PUSH signal.

14) MOVE signal turns OFF at the same time as or within 10ms after PEND signal turns ON.

Ɣ Example of operation (Normal positioning operation)

For the general positioning operation, set the signal in Step 6) to OFF.

When the remaining travel distance becomes within the range of the positioning width set in the

position data, and the CSTR signal is turned OFF, the PEND signal is turned ON.