IAI America MSCON User Manual

Page 98

Advertising
background image

3.4 Fieldbus

Type

Address Map

90

3.4.3 Gateway Control Signals (in common for all operation modes)

When operating the system with Fieldbus, the axes are controlled via MSCON. The top 2 words

of input and output in each operation mode are the signals Gateway control and status

monitoring.



(n is the top word address for each PLC input and output between MSCON and PLC)

PLCĺMSCON (PLC Output)

MSCONĺPLC (PLC Input)

Control Signal 0

n

Status Signal 0

n

Control Signal 1

n+1

Status Signal 1

n+1



(1) PLC I/O Signal

PLC Output




Address n

b15 b14 b13 b12 b11 b10

b9

b8

b7

b6

b5

b4

b3

b2

b1

b0

Control

Signal 0

M

O

N

R

TE







Address n+1

b15 b14 b13 b12 b11 b10

b9

b8

b7

b6

b5

b4

b3

b2

b1

b0

Control

Signal 1

(to be fixed to

0)䎃

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0


PLC Input

Address n

b15 b14 b13 b12 b11 b10

b9

b8

b7

b6

b5

b4

b3

b2

b1

b0

Status

Signal 0

RUN

LERC

ERR

T

M

O

D

A

LM

H

A

LM

L

EMG

ALMC128

ALMC64

ALMC32

ALMC16

A

LM

C

8

A

LM

C

4

A

LM

C

2

A

LM

C

1





Address n+1

b15 b14 b13 b12 b11 b10

b9

b8

b7

b6

b5

b4

b3

b2

b1

b0

Status

Signal 1

MNT5

MNT4

MNT3

MNT2

MNT1

MNT0

LN

K

5

LN

K

4

LN

K

3

LN

K

2

LN

K

1

LN

K

0





Output of communication available axis number

Output of alarm-issued axis number

1 word=16 bit

Signal to cancel the remained condition of communication error

(ERR-T/ERR-C) during an operation

Signal to activate operation control by communication

1 word=16 bit

Each type of control status monitoring output signals