Modbus – IAI America ROBO Cylinder Series User Manual

Page 113

Advertising
background image

5. Modbus RTU

105

Modbus

5.3.19 Special Input Port Input Signal Status Reading<<SIPM>>

(1) Function

This bit reads the status of input ports other than the normal input port.

[Refer to 4.3.2 (16), “Data of special input port monitor registers” for the data input via the special

input port.]

(2) Query format

Field

Number of data items

(number of bytes)

RTU mode

8-bit data

Remarks

Start

None

Silent interval

Slave address [H]

1

Arbitrary

Axis number + 1 (01

H

to 10

H

)

Function code [H]

1

03

Register reading

Start address [H]

2

9012

Special input port monitor

Number of registers [H]

2

0001

Reading addresses 9012

H

Error check [H]

2

CRC (16 bits)

End

None

Silent interval

Total number of bytes

8

(3) Response format

A response message contains 16 bits of data per register.

Field

Number of data items

(number of bytes)

RTU mode

8-bit data

Remarks

Start

None

Silent interval

Slave address [H]

1

Arbitrary

Axis number + 1 (01

H

to 10

H

)

Function code [H]

1

03

Register reading

Number of data bytes [H]

1

02

Reading 1 register = 2 bytes

Data [H]

2

Special port monitor Refer to 4.3.2 (16), “List table.”

Error check [H]

2

CRC (16 bits)

End

None

Silent interval

Total number of bytes

7