7. T

roubleshooting

306

Modbus

7.3 When Communication Fails

Select an applicable item and perform the processing enclosed with †.

The specific processing details are explained after the flowchart; check the details indicated by the *

symbol.

{

= Yes, X = No

Symptom: Cannot communicate normally!

Was communication possible until now?

Continue to the next page

Cannot communicate with all controllers?

Cannot communicate with any controllers. o

Cannot communicate with specific controllers. o

(1) Host failure o Repair host

(2) Disconnection of communication cables

or poor contact due to vibration and

similar o Fix disconnection

(1) Controller failure o Replace the controller

(2) Disconnection of communication cables between

controllers and junctions o Fix disconnection

(3) Dislocation of terminating resistor o Fix dislocation

(4) Wrong controller axis number setting (when

controllers are replaced, parameters are initialized,

the version is upgraded, etc.) o Check *4

(5) Wrong controller communication speed setting (when

controllers are replaced, parameters are initialized,

the version is upgraded, etc.) o Check *6

(6) Wrong transmitter activation time setting (when

controllers are replaced, parameters are initialized,

the version is upgraded, etc.)

o

Check parameter No. 17

Can any of the parts of the communication cables be moved?

There are movable parts o Disconnection of communication cables o Fix disconnection

Is the power supply voltage to each device normal? (each RC controller, SIO converter, etc.)

Power supply voltage error o Set normal power supply voltage

Did the failure occur after the surrounding environment was changed? (Peripheral devices, etc. have been changed.)

Occurred after change o Malfunction due to noise

o

(1) Decrease the communication speedo Check *2
(2) Change communication cable wiringo Check *7
(3) Check connection of FG of each RC controller *7
(4) Mount a clamp filter on the power lines
(5) Check grounding of the control board *7