6. Modbus
ASCII
249
Modbus
(4) Sample query
A sample query that pauses a controller of axis No. 0 is shown below.
Query: 01 05 04 0A FF 00 ED
Field
ASCII mode 8-bit data
Converted ASCII
code data [H]
Start
‘:’
3A
Slave address [H]
‘0’, ‘1’
3031
Function code [H]
‘0’, ‘5’
3035
Start address [H]
‘0’, ‘4’, ‘0’, ‘A’
30343041
Changed data [H]
‘F’, ‘F’, ‘0’, ‘0’
46463030
Error check [H]
‘E’, ‘D’ (in accordance with LRC calculation) 4544
End
‘CR’, ‘LF’
0D0A
If the change is successful, the response message will be the same as the query.