Data and status reading (queries using code 03), Modbus – IAI America ROBO Cylinder Series User Manual

Page 71

Advertising
background image

5. Modbus RTU

63

Modbus

5.3. Data and Status Reading (Queries Using Code 03)

5.3.1 Reading Consecutive Multiple Registers

(1) Function

These registers read the contents of registers in a slave.

This function is not supported in broadcast communication.

(2) Start address list

With RC Series controllers, the sizes of send/receive buffers are set to 256 bytes, respectively.

Accordingly, a maximum of 125 registers’ worth of data consisting of 251 bytes (one register uses

two bytes), except 5 bytes (slave address + function code + number of data bytes + error check) of

the above 256 bytes, can be queried in the RTU mode. In other words, all of the data listed below

(total 21 registers) can be queried in a single communication.

It is also available to refer to multiple registers of the addresses in a row at one time of sending

and receiving.

Address [H] Symbol

Name

Sign

Register size

Byte

0500

ALA0

Alarm detail code

1

2

0501

ALA0

Alarm address

1

2

0502

-

Always 0

-

1

2

0503

ALC0

Alarm code

1

2

0504,0505

ALT0

Alarm occurrence time

2

4

8400,8401

TLMC Total moving count

(Note1)

2

4

8402,8403

ODOM Total moving distance

(Note1)

2

4

841A,841B

TIMN

Present time(dedicated for SCON-CA)

2

4

8420,8421

TIMN

Present time

(dedicated for PCON-CA/CFA)

2

4

842E,842F

TFAN Total fan driving time

(dedicated for PCON-CFA)

2

4

9000, 9001

PNOW Current position monitor

{

2

4

9002

ALMC Present alarm code query

1

2

9003

DIPM

Input port query

1

2

9004

DOPM Output port monitor query

1

2

9005

DSS1 Device status query 1

1

2

9006

DSS2 Device status query 2

1

2

9007

DSSE Expansion device status query

1

2

9008, 9009

STAT

System status query

2

4

900A, 900B VNOW Current speed monitor

{

2

4

900C, 900D CNOW Current ampere monitor

{

2

4

900E, 900F

DEVI

Deviation monitor

{

2

4

9010, 9011

STIM

System timer query

2

4

9012

SIPM

Special input port query

1

2

9013

ZONS Zone status query

1

2

9014

POSS Position complete number status query

1

2

9015

SSSE Expansion system status register

1

2

901E

FBFC Force feedback data monitor

{

2

4

Note 1 Dedicated for PCON-CA/CFA, SCON-CA and ERC3