1 message frames (query and response), Modbus – IAI America ROBO Cylinder Series User Manual

Page 187

Advertising
background image

6. Modbus

ASCII

179

Modbus

6.1 Message Frames (Query and Response)

Start

Address

Function code

Data

LRC Check

End

1 character

2 characters

2 characters

n characters

2 characters

2 characters

1 byte

2 bytes

2 bytes

nx2 bytes

2 bytes

2 bytes

* 1 character is expressed with 1 byte (2 characters) in ASCII code (refer to 6.2 ASCII “Code

Table”).

(1) Start

The Start field is equivalent to the header field and “:” (colon) is used in the ASCII mode.

It is expressed as 3A

H

in ASCII code.

(2) Address

This field specifies the addresses of connected RC controllers (01

H

to 10

H

).

Set Address = axis number + 1

in ASCII code. Example) The axis number/is 30

H

32

H

.

Note: The address is not equal to the corresponding axis number: be careful when making settings.

(3) Function

The table below summarizes the function codes and functions that can be used with RC controllers.

Code

[Hex] (ASCII)

Name

Function

01

H

30

H

31

H

. Read Coil Status

Read coils/DOs.

02

H

30

H

32

H

. Read Input Status

Read input statuses/DIs.

03

H

30

H

33

H

. Read Holding Registers

Read holding registers.

04

H

30

H

34

H

. Read Input Registers

Read input registers.

05

H

30

H

35

H

. Force Single Coil

Write one coil/DO.

06

H

30

H

36

H

. Preset Single Register

Write holding register.

07

H

30

H

37

H

. Read Exception Status

Read exception statuses.

0F

H

30

H

46

H

. Force Multiple Coils

Write multiple coils/DOs at once.

10

H

31

H

30

H

. Preset Multiple Registers

Write multiple holding registers at once.

11

H

31

H

31

H

. Report Slave ID

Query a slave’s ID.

17

H

31

H

37

H

. Read / Write Registers

Read/write registers.

* This manual uses

mark function codes.

* The ROBONET gateway supports three types of function codes (03

H

, 06

H

and 10

H

).

(Refer to the separate ROBONET Instruction Manual.)

The ROBONET gateway does not support the ASCII mode.