Modbus – IAI America ROBO Cylinder Series User Manual
Page 133
Advertising
5. Modbus RTU
125
Modbus
(4) Query sample
A sample query that pauses a controller of axis No. 0 is shown below.
Query (silent intervals are inserted before and after the query)
01 05 04 0A FF 00 AD 08
Field
RTU mode
8-bit data
Start
Silent interval
Slave address [H]
01
Function code [H]
05
Start address [H]
040A
Changed data [H]
FF00
Error check [H]
AD08 (in accordance with
CRC calculation)
End
Silent interval
If the change is successful, the response message will be the same as the query.