5. Modbus RTU

124

Modbus

5.4.6 Pause <<STP>>

(1) Function

If the pause command is transmitted during movement, the actuator decelerates and stops. If the

status is set back to normal again, the actuator resumes moving for the remaining distance.

As long as the pause command is being transmitted, all motor movement is inhibited.

If the alarm reset command bit is set while the actuator is paused, the remaining travel will be

cancelled.

If this bit is set during home return, the movement command will be held if the actuator has not yet

reversed after contacting the mechanical end. If the actuator has already reversed after contacting

the mechanical end, home return will be repeated from the beginning.

(2) Query format

Field

Number of data items

(number of bytes)

RTU mode

8-bit data

Remarks

Start

None

Silent interval

Slave address [H]

1

Arbitrary

Axis number + 1 (01

H

to 10

H

)

00

H

when broadcast is

specified

Function code [H]

1

05

Write to a single coil DO.

Start address [H]

2

040A

Pause command

Changed data [H]

2

Arbitrary

Pause command: FF00

H

Normal : 0000

H

Error check [H]

2

CRC (16 bits)

End

None

Silent interval

Total number of bytes

8

(3) Response

If the change is successful, the response message will be the same as the query.