background image

4. Communication

29

Modbus

4.2 Timeout and Retry

After sending a query, the host waits for a response from the controller (except when the query

that has been sent is a broadcast query).

If the elapsed time after sending a command until a response is received exceeds the timeout

value (Tout), the host may send the command again to reestablish communication. If the

number of retries exceeds three times, it means that an irremediable communication error has

occurred.

The method for calculating the timeout value (Tout) is explained below.

1. Timeout value (Tout)

Tout = To + D + (10 x Bprt/Kbr) [ms]

To : Internal processing time* x Safety factor (3)

D

: Min. delay for activating local transmitter [ms]

(default value of parameter No. 17 is 5 ms)

Kbr : Baud rate [kbps]

Bprt : Response message bytes + 8

Caution The internal processing time varies depending on the category of the register

to be accessed. The processing time required for each action is listed in the

table below.

Item

Maximum time [ms]

Read/write a register other than those in the low-speed memory area

1

Position data (1 position) Read

4

Position data (1 position) Write

15

Position data (1 position) Read/write

18

Position data (9 positions) Read

9

Position data (9 positions) Write

90

Position data (9 positions) Read/write

98

2. Number of Retries

Nrt = 3 (note that setting of the number of retries is mandatory)