1 touch interface data – Proface FP3900 - 19 Flat Panel" User Manual

Page 64

Advertising
background image

5-9

FP-2500/FP-2600 Series User Manual

5.1 Touch Interface Data

Touch the desigated positions, one after
the other. Correction data will be
calculated from the difference between the
actual and the theoretical values.

The actual value is shown on the display.

2)

Press the [Esc] key to terminate
the program. Press the [Y] key
after the message on the left is
shown, and the program will
terminate without saving any
FPcalibration data. If the [N] key
is pressed, the system will return
to "FPcalibration mode".

3)

4)

Enter the file name

When the data filename is speci-
fied from the parameter (-C=
[path]) during the execution of
FPCALIB.EXE, the program will
terminate without showing the mes-
sage on the left.

Analog Touch Panel Calibration FPCALIB.EXE

Version 1.** Copyright (c) 2000 Digital

Electronics Corporation

Calibration Mode

Touch upper left and lower right corner of the

screen.

[Enter : Go to test mode.

[Esc] : Terminate program.

Upper left Lower right

(0039.0026) (0997.0988)

Terminate program without saving calibration data?(Y/N)

Calibration data name? FPATPH.CAL_

• Do not touch two points at the

same time.

• Touch right above the designated

position.

• By re-touching the points, the ac-

tual coordinates will redisplay.

The "test mode" tests whether the
FPcalibration has been processed
correctly or not. To enter "test mode",
press the [Enter] key.
The FPcalibration is confirmed as suc-
cessful if the locus shown on the display
matches as touched. Otherwise, return
to the "FP calibration mode" and redo the
FPcalibration by touching the right blink-
ing position.

Press the [Esc] key to return to
"FPcalibration mode".

If the test result is OK, press the [Enter]
key. After the following message appears,
enter the name of the data file and press
the [Enter] key.

Analog Touch Panel Calibration FPCALIB.EXE

Version 1.**

Copyright(c)2000 Digital Electronics Corporation

Test Mode

[Enter] : Save calibration data and Exit.

[Esc] : Return to calibration mode.