7.2 Periodic Check Points

• The gasket must be inserted correctly into the groove for the FP unit’s

moisture resistance to be equivalent to IP65f.

• Be sure the gasket's seam is not inserted into any of the unit's cor-

ners, only in the straight sections of the groove. Inserting it into a
corner may lead to its eventually tearing.

• The upper surface of the gasket should protrude approximately 2mm

out from the groove. Be sure to check that the gasket is correctly in-
serted before installing the FP into a panel.

To keep your FP unit in its best condition, please inspect the following points periodi-
cally.

FP Operation Environment

Is the ambient temperature within the allowable range (0

o

C to 50

o

C )?

Is the ambient humidity within the specified range (30%RH to 90%RH, dry
bulb temperature of 39

o

C or less)?

Is the operating atmosphere free of corrosive gasses?

Electrical Specifications

• Is the Rated Voltage Range appropriate ?

Related Items

• Are all power cords and cables connected properly? Have any become loose?

• Are all installation fasteners holding the unit securely?

• Are there any scratches or traces of dirt on the installation gasket?

7.2 Periodic Check Points

unit: mm [in.]

2.0 [0.08]

FP Model Number

Rated Voltage Range

FP2500-T12
FP2600-T12

AC85 to 264V

FP2500-T42-24V
FP2600-T42-24V

DC19.2 to 28.8V