1 overview, 2 pre-installation tasks, 2.1 overview – Innotech eServer User Manual

Page 20: 2.2 remote access, ports and security information, 1 overview 2-2 pre-installation tasks

Advertising
background image

eServer Setup and Site Installation Instructions

Page 20

© Mass Electronics Pty Ltd 2009

Edition 5.0 dated 07/01/2014

2-1 Overview

This section provides an overview of the steps required for the installation and basic configuration

of the eServer software onto a computer, and installation of the additional Magellan Crystal Report

additions if required.

2-2 Pre-installation Tasks

2-2.1 Overview

Prior to installing eServer v1.20 or greater there are a series of pre-installation tasks to undertake.

This includes gathering all the required information to make the installation process easier, and

preparing site computer security settings to facilitate an easy setup process.

2-2.2 Remote Access, Ports and Security Information

2-2.2.1 Internet Access

You may use an existing and available Broadband Cable/ADSL Internet Connection, however in this

scenario the site will

need to have a DNS name or static IP address setup through the Internet

Service Provider (ISP), and also allow the opening of Ports through their Firewall / Router.

The installation program for eServer v1.20 or greater automatically creates and configures the necessary web page

files on your computer in the location c:\MyWebPages. Once eServer and the ATOM Reports Component (if required)

have been installed, you will have to check the security settings for c:\MyWebPages and your computer's Internet

Information Services Settings.

See the following for more information:

2-5 Security Access to the c:\MyWebPages Directory

• Chapter 3 - Configuring Internet Information Services (IIS)

NOTE

If the site IT Staff deny the setup of required ports, a separate ADSL internet connection will need to be provided to a

dedicated computer. This computer can be configured with a Static External IP address and configured to have Port

Forwarding. In this instance, IT Staff will only need to enable Port 80 for internet connection and accept outgoing

connections on 1433, 20000 and 20001, not incoming through their own Firewalls. Regardless, the computer running

eServer and iComm needs to have the full incoming and outgoing connections to the Ports setup.

NOTE

Many of the processes within the Pre-installation Tasks assume a moderate to high degree of technical IT expertise. It is

recommended to consult with the site IT Manager for assistance and site specific security settings where required.