Alarm Setup

This screen allows for hard contact Alarm inputs to be named and to set responses and durations.

Email Address
This will be the destination email address for all email messages regarding Alarm inputs 1 to 10.

Name
This Name will appear in all logs and emails regarding the Alarm inputs 1 to 10.

NC:
The default condition is set for Normally Open (NO). A closed Alarm contact input will trigger
Alarms. Check this box to change to a Normally Closed condition.

Log:
Click the Log check box to have the Alarms recorded in the Event Log.

Alert Select
Click the Alert check box to have an XML message send to an Event server. The destination
address and port number are determined by the Master Admin in IP Setup.

Email Select
Click this box to send an email when an Alarm occurs to the address programmed at the top of
the page.

Email Event Log Select
When this box is checked the entire Event Log will be sent to the Address provided in the Email
Event Log screen. Caution: Due to the size of the log, this can up to 1 minute to send. During this
period new events will not be recorded in the log until the transfer is complete. In situations
where hardware contact alarms occur frequently checking this box must be done with caution.

Auxiliary Assignment and Duration
For each alarm input, the operator can assign
two auxiliary outputs and corresponding
durations. In the case where one contact output
has been assigned to two different alarm inputs
and the auxiliary output will respond to the first
alarm occurrence.