2.1.1

Layout of Cabinets

Figure 2-2: Layout of Cabinets (typical)

2.2

Electrical Specifications

Table 2-1: Electrical Specifications for the MGE Galaxy 5000

Output Power Rating (0.9 PF)

40KVA

50KVA

60KVA

80KVA

100KVA

130KVA

UPS Voltage (input/output)

480/480

480/480

480/480

480/480

480/480

480/480

Input/Output Requirements & Frequency

Three phase, Three wire + G, 60Hz

Input Phase Rotation

A, B, C Clockwise

Input Power Factor

> 0.98

Input Current/Input Current with Battery
Charging Current

48A/59A

59A/70A

71A/88A

94A/111A 117A/150A

151A/182A

Maximum Input Current with Charging Current
(at low line -10%)

57A

70A

85A

111A

148A

182A

Bypass/Output Current

48A

60A

72A

96A

120A

156A

Battery Voltage

356VDC End Voltage 432VDC Nominal 490VDC Max. Floating Voltage

Max. Battery Current at Battery Voltage
(432 VDC at 100% Load)

90A

113A

135A

180A

225A

293A

Max. Battery Current at End-Voltage
(356 VDC at 100% Load)

109A

137A

164A

219A

273A

355A

Battery Disconnect Circuit Breaker Rating

175A, 250A, 400A

Input, Bypass, Maintenance Bypass and
Output Switch Rating

125A

250A

Input and Output Fuse Rating

160A

315A

DISTRIBUTION

TRANSFORMER

MBC

TOP VIEW

UPS

BATTERY

MGE Galaxy 5000

Setup and Installation

2 — 2

86-174010-00 B00