2.4

Redundant Parallel Configuration (Maximum Two UPS Units for Pn)

These configurations do not have an external System Bypass Cabinet (SBC).

Figure 2-5: Parallel UPS With Common Normal and Bypass AC Inputs

Figure 2-6: Parallel UPS With Separate Normal and Bypass AC Inputs

CAUTION

If the two UPSs are placed side by side, connect as indicated above. In the other
configurations, always make sure that the cables between the UPSs and bypass
AC source have the same cross-section and the same length. The same is true
for the cables between the UPSs and the load.

To access the connections, remove cover
(see Section 1.3).
1 - The grounding conductors must be

connected to the grounding-plate of each
UPS (17).

2 - Connect the three phases of the normal

AC source to connection (16) in each UPS.

3 - Connect the three phases of the bypass AC

source to connection (15) in each UPS unit.

4 - Connect the three phases of the supplied

loads to connection (14) in UPS1.

5 - Connect (14) in UPS2 to (14) in UPS1

using the three load conductors.

6 - Connect the external battery (+/-) to

connections (22) in UPS1 and UPS2.

7 - Tie the cables down to the cabinet frames.
8 - Put the covers back in place.

To Load

To Bypass
AC Source

To Normal
AC Source

UPS 1

UPS 2

14.56”

22

14.56”

22

Ground

To access the connections, remove cover
(see Section 1.3).
1 - The grounding conductors must be

connected to the grounding-plate of each
UPS (17).

2 - Connect the three phases of the bypass

AC source to connection (15) in each UPS.

3 - Connect the three phases of the supplied

loads to connection (14) in UPS1.

4 - Connect (14) in UPS2 to (14) in UPS1

using the three load conductors.

5 - Connect the external battery (+/-) to

connections (22) in UPS1 and UPS2.

6 - Tie the cables down to the cabinet frames.
7 - Put the covers back in place.

To load

To load

To Load

14.56”

14.56”

To Normal / Bypass

Ground

AC Source

UPS 1

UPS 2

22

22

MGE Galaxy 5000

Setup and Installation

2 — 4