Installation and user manual – APC MGE GALAXY 5000 40 130KVA User Manual

Page 33

Advertising
background image

Installation and User Manual

2.9

Routing the Control/Communications Cables

Single UPS

Figure 2-14: Routing the Control/Communications Cables for Single UPS

CAUTION

To ensure sufficient isolation of control and communication cables, they must
be run separately from the power cables. Reinforce the insulation of these control
and communication cables if any risk of contact with the power cables exists.

Cable description

Insulation level

Location on illustration

Relay communication card

SELV

3

Optional communication card

SELV or LV

4

External battery circuit-breaker cables

SELV

6

General-shutdown cable

SELV

7

Tie

Ties

Separate the control and communication
cables from the power cables.
Run the cables together in front of the
protection panels and tie them to the
panels as indicated.

General-shutdown cable (not supplied)
and external battery circuit breaker cable
must be tied down separately.

Free slots for optional communication
cards. See installation drawing for proper
card placement.

Slot for relay communications card

Setup and Installation

2 — 11

86-174010-00 B00