MGE Galaxy 5000

A — 4

86-174010-00 B00

General characteristics of Galaxy 5000 UPSs

INFORMATION

The operating temperature range is 32°F to 104°F (0°C to +40°C); for overload
conditions is 32°F to 86°F (0°C to +30°C). Optimum operating range is within 68°F
to 77°F (20°C to +25°C). Battery backup time is adversely affected by high and low
temperatures. It is significantly reduced at temperatures under 50°F (10°C). Above
77°F (25°C), battery service life is cut in half every 18°F (10°C). Above 104°F (40°C),
battery manufacturers no longer guarantee operation due to the risk of thermal
runaway.

UPS power in KVA

40

50

60

80

100

130

Normal AC input

Number of conductors

3 phases + ground

Reference voltage at Pn

432 V to 528 V

Reference frequency

45 Hz to 65 Hz

THDI

Typically 3% at Pn

Power factor

>0.99

Bypass AC input

Number of conductors

3 phases + ground

Reference voltage at Pn

432 V to 528 V

Reference frequency

45 Hz to 65 Hz

Load output

Number of conductors

3 phases

Set phase-to-phase voltages

480 V

Voltage variation

± 1%

Adjustable frequencies and
tolerance (on battery power)

60 Hz ± 0.1 Hz

Voltage variation for 0 to
100% load step change

± 1%

Permissible overloads

150% for 1 minute, 125% for 10 minutes

THDU Ph-to-Ph and Ph-to-N
for nonlinear load

< 2% Ph-to-Ph

Battery

Standard battery technology

Sealed lead-acid battery (gas-recombination)

Inverter

Active power (kW)

36

45

54

72

90

117

Heat losses in kW Heat
Heat losses in BTUs

2.71
9250

3.39
11560

4.06
13870

5.42
18500

5.74
19610

7.47
25490

Storage temperature range

-13°F to 103°F (-25°C to +45°C)

Relative humidity

20% to 95%

Maximum operating altitude
without derating

3281 ft (< 1000 m)

Operating temperature range
at Pn

32°F to 104°F (0°C to 40°C)