Installation and User Manual

2.5

Auxiliary Interconnections Between UPSs in Parallel Configurations

Figure 2-7: Redundant Parallel Configuration (Maximum Two UPS)

Exchange-current interconnections (19):
Link connectors XMS02 and XMS03 on the
two UPS units.
CAN // interconnections (21):
Fit a blue plug on connector XMS06 on
UPS1. Link connector XMS07 on UPS1 to
connector XMS06 on UPS2. Fit a red plug
on connector XMS07 on UPS2.

Note: The supplied cables (33 ft) limit the
distance between the two UPS units to
approximately 20 ft.

UPS 1

PCA INTN

19

19

19

19

21

21

21

21

PCA INTN

UPS 2

Blue
plug

Red plug

Setup and Installation

2 — 5