Installation and user manual – APC MGE GALAXY 5000 40 130KVA User Manual

Page 41

Advertising
background image

Installation and User Manual

Battery

3.9

Display Messages List

Low battery warning threshold if battery monitor
inactive

40% remaining backup time

20 - 60 - 80 % remaining
backup time

Low battery warning threshold if battery monitor
active

4 minutes of battery backup
time

1 to X minutes of battery
backup time

Interval between two battery tests

30 days

1 to 180 days

Operation

3 — 7

86-174010-00 B00

Fault of downgraded mode
Internal CAN communication fault
External CAN communication fault
CAN communication relay fault
UPSs not connected by CAN cable
Resynchronizing
CAN communication resynchronization fault
Loss of communication with UPS 1
Loss of communication with UPS 2
Loss of communication with UPS 3
Loss of communication with UPS 4
Loss of communication with UPS X

Fault, filtering of customer communication
Customer communication disabled

Generic fault on equipment
Emergency Power Off (EPO)
UPS personalization fault
Personalization does not match UPS
Transfer to bypass disabled

Major Fault on subassembly
Charger fault
Bypass static switch fault
PFC fault
Inverter fault
Power supply board fuse blown
Fan fault
TVSS fault

Internal and external switches
Q3BP switch closed
Q5N switch open
Q4S switch open
External Q3BP switch closed (MBC or SBC CB1)
External Q5N switch open (MBC or SBC CB2)
External Q4S switch open (MBC CB3)
Abnormal bypass operation
Abnormal external bypass operation

Fault or state of installation
Installation overload
Non-redundant installation
Inverter starting
Not enough inverters for load connection
Not enough bypass static switches
Inverter ready for load connection

Fault or state on Normal AC
Q1 switch open
Normal AC source downgraded
Normal AC input phase rotation fault
Normal AC fuse blown
Normal AC source static switch failure
Normal AC source outside tolerances
Normal AC backfeed (KA1) is open
Normal AC backfeed (KA1) fault

Fault or state on Bypass AC or Bypass Static Switch
Bypass source present
Bypass static switch overload
AC Bypass static switch thermal overload
Bypass input phase rotation fault
Bypass source outside tolerances
Bypass AC backfeed (KA2) is open
Bypass AC backfeed (KA2) fault

Fault or state for PFC
PFC overload
PFC thermal overload
Starting

Fault or state standard charger
Low battery warning
Low battery shutdown
Battery circuit breaker open (QF1) (Battery Cabinet #1 or #3)
Battery circuit breaker 2 open (QF2) (Battery Cabinet #2 or #4)
End of theoretical battery service life
Battery temperature fault
Battery deep discharge
Battery room temperature fault
Battery test result not OK
Battery test in progress
Charger shutdown by PFC overload

Fault or state inverter
Inverter current limiting
Inverter overload
Inverter thermal overload
Inverter fuse blown
Inverter and bypass desynchronized

Fault or state load
Abnormal presence of output voltage
Load short circuit

Fault or state external synchronization
External sync frequency outside tolerances
UPS on external synchronization