2.8.1

Characteristics of the Contacts on the Relay Communications Card

Figure 2-13: Characteristics of the Contacts on the Relay Communications Card

Communications Card Connection Example

If a SELV (safety extra low voltage) source is used, it must always be possible to isolate the communications card from
the upstream source to ensure the safety of personnel working on the installation.

Disconnecting device that can be locked

AC

communication
card

UPS OFF

UPS ON

Low battery warning

Load on battery power

Load on automatic bypass

Load on UPS

Battery fault

General alarm

Characteristics of the output contacts:
Permissible voltage: 250V AC, 30V DC.
Permissible current: 2 A.
Cable: 4 x 0.93 mm2, Ø 6.6 ± 0.3 mm.

Characteristics of the input contacts:
Switched voltage: 5 V DC
Consumption: 10 mA.
Cable: 4 x 0.34 mm2, Ø 5 ± 0.5 mm.

MGE Galaxy 5000

Setup and Installation

2 — 10

86-174010-00 B00