Parallel UPS

Figure 2-15: Routing the Control/Communications Cables for Parallel UPS

CAUTION

To ensure sufficient isolation of exchange-current, CAN and external bypass
cabinet cables, they must be run separately from the power cables. Reinforce
the insulation of these control and communication cables if any risk of contact
with the power cables exists.

Cable description

Insulation level

Location on illustration

External bypass cabinet cable

ELV

1

CAN cables

SELV

1

Exchange-current cables

SELV

1

Relay communication card

SELV

3

Optional communication card

SELV or LV

4

External battery circuit-breaker cables

SELV

6

General-shutdown cable

SELV

7

Ties

Ties

Parallel-connection cables for connection
to the SBC (not supplied). The CAN and
current exchange cables are supplied.

Slot for relay communications card

Free slots for optional communication
cards. See installation drawing for proper
card placement.

General-shutdown cable (not supplied)
and external battery circuit breaker cable
must be tied down separately.

Separate the control and communication
cables from the power cables.
Run the cables together in front of the
protection panels and tie them to the
panels as indicated.

MGE Galaxy 5000

Setup and Installation

2 — 12

86-174010-00 B00