When sizing the upstream circuit breakers, the parameters presented below must be taken into account:
Time/current curves for UPS input and output fuses:

UPS short-circuit current with inverter coupled and By-pass AC source out of tolerances

Line Current Values

Rated power of
each UPS unit

Continuous input
current at V=480V

Input current at
V=480V overload
= 1.25 In limited to
10 min.

Input current at
V=480V overload
= 1.5 In limited to
1 min.

Input/output fuse
ratings

40KVA

48 A

60 A

72 A

160 A

50KVA

60 A

75 A

90 A

160 A

60KVA

72 A

90 A

108 A

160 A

80KVA

96 A

120 A

144 A

160 A

100KVA

120 A

150 A

180 A

315 A

130KVA

156 A

195 A

234 A

315 A

Sn

40KVA

50KVA

60KVA

80KVA

100KVA

130KVA

In

48 A

60 A

72 A

96 A

120 A

156 A

Limitation

230 A

230 A

230 A

260 A

435 A

435 A

40-80 kVA: 160A

100-130 kVA: 315A

I (A)

t (s)

10

10

2

10

3

10

4

10

10

-1

1

10

2

10

-2

10

3

10

-3

10

4

10

-4

MGE Galaxy 5000

Appendices

A — 2

86-174010-00 B00