Mge galaxy 5000 – APC MGE GALAXY 5000 40 130KVA User Manual

Page 40

Advertising
background image

3.8

UPS Personalization

Access to the Personalization Functions

CAUTION

Personalization must be carried out with switches Q1 (8) and Q5N (11) open (OFF)
and switch Q4S (9) closed (ON).

Figure 3-8: UPS Personalization

Personalization Settings

Operating Mode

Frequency

Automatic Bypass

Transfer to bypass AC source

Enabled

Disabled – disabled when
limiting

Transfer to bypass with bypass AC source out of
tolerances

Enabled

Disabled

UPS output frequency

60 Hz

60Hz

Tolerance for bypass AC source

8 %

0.5 - 1 - 2 - 4 %

Synchronization speed with bypass AC source

2 Hz / s

1 Hz / s

Function

Factory setting

Options

UPS operating mode

NORMAL

UPS automatic start

Disabled

Enabled

Authorized number of starts

4

1 to 255

Delay before reset of number of executed
automatic starts

4 seconds

1 to 60 seconds

The password

To change the password, see the Settings menu.

1 - Press the menu key (36).
2 - Select "Settings", then "Personalization" using the
function keys (35) or .
3 - Confirm by pressing the function key (35) .
4 - Enter the password by successively selecting each icon
using the corresponding function key.
5 - Confirm by pressing the function key (35) .
6 - To save the personalization settings, confirm by
pressing the function key (35) .

is factory set.

MGE Galaxy 5000

Operation

3 — 6

86-174010-00 B00