Operation – APC MGE GALAXY 5000 40 130KVA User Manual

Page 35

Advertising
background image

Operation

3 — 1

86-174010-00 B00

Operation

CAUTION

All operations concerning system start-up and compliance with standards and
regulations, including those related to the battery cabinet, must be carried out
by trained and certified personnel before using the UPS.

3.0

Scope

Provides startup, shutdown, and normal operation of the MGE Galaxy 5000 UPS. Describes the operation of the
mimic-panel LEDs.

3.1

Shutting Down a Single UPS

The UPS remains energized unless it is shut down.

Figure 3-1: Shutting Down a Single UPS

1 - Press a button to exit sleep mode.
2 - Press the OFF button (38) for 3 seconds.

The load is no longer protected by the UPS. It is
supplied via the bypass.

3 - Set the battery circuit breaker of the auxiliary cabinets

to OFF.

4 - Set the input switch Q1 (8) to OFF.

The charger no longer operates to keep the batteries
fully charged.

5 - Open the upstream circuit breakers of the Normal AC

source and Bypass AC source to completely power off
the UPS.