Status Bits for Siemens Modems & Internal Modem

Bit 1

CPIN Command Failed: This command is used to unlock the SIM. This bit will be set if supplied PIN

is invalid or SIM is blocked or modem fails to respond within 2 sec of
sending this command. This command is NOT executed if SIM Pin code is
not enabled.

Bit 2

CSCA service center number command Failed: This command is used to set the SMS service

center number. This bit will be set if setting SMS service center number
command fails or modem fails to respond within 2 sec of sending this
command. This command is NOT executed if Service center number is
not provided.

Bit 3

CREG Command Failed: This command is used to register mobile device to the GSM network. This

bit will be set if registration fails or modem fails to respond within 2 sec of
sending this command.

Bit 4

CMGF Command Failed: SMS format selection command. This bit is set if modem returns Error

response to this command or modem fails to respond within 2 sec of
sending this command.

Bit 5

CNMI Command Failed: Command used to check newly received SMS message. This bit is set if

modem returns Error response to this command or modem fails to
respond within 2 sec of sending this command.

Bit 6

CSQ Command Failed: This command is used to get signal strength. This bit is set if modem

returns Error response to this command or modem fails to respond within
2 sec of sending this command.

Bit 7

COPS Command Failed: This command is used to select and register to a GSM network operator.

This bit is set if modem returns Error response to this command or modem
fails to respond within 2 sec of sending this command.

Bit 8

CPEE Command Failed: This command (CMEE) is used to disable mobile equipment (ME) error

indication. This bit is set if modem returns Error response to this command
or modem fails to respond within 2 sec of sending this command.

Bit 9

ATE Command Failed: This bit will be set if Echo off command to Modem returns Error or modem

fails to respond within 2 sec of sending this command.

Bit 10

CSMP Command failed: This bit will set if "Set SMS text mode parameter" command to Modem

returns error or Modem fails to respond within 2 Sec of sending this
command.

Status Bits for User Specific Initialization

Bit 1 – Bit 12

If command(s) fails in the user script, a corresponding bit is set indicating failure. For example: Bit 1 is
set when the first command in the script fails. Bit 2 is set when the 2nd command in the script fails.

SMS Message Buffer Register Settings

The Message Buffer Register holds the latest SMS message string sent or received by the controller. An individual SMS message
can have up to 160 characters.

Message Buffer Register Settings

Address

Enter the starting register location where the latest SMS message string is stored. This is a block of
80 registers that are consecutive in memory. For example, if you are using R101– R180, you need to
enter the starting register address as %R0101.

Name

Enter (or select) an I/O Name.


SMS Configuration Parameters

Configuration Parameters

Center Number

If required, select the box and type in Center number (up to 16 digits). The Center Number uses
numbers 0 – 9 and these special characters: , ( ) – +

SIM Pin Code

If required, select the box and type Pin number (up to 4 digits). SIM Pin Code can have only digits 0
– 9.

Command Interval

This is the interval of time (in seconds) that the OCS poll for messages (valid range: 1 - 100).


Note: SMS service center number should be configured correctly to send a SMS successfully.