4 lau_config_getdilmode (0x010e), Lau_config_getdilmode (0x010e) – Beijer Electronics SCOM RBC EN User Manual

Page 26

Advertising
background image

Command Reference

26

Beijer Electronics, MAEN993

5.6.4 LAU_CONFIG_GETDILMODE (0x010E)

DIL Switch Mode

For a base configuration, Beijer Electronics RBCs are equipped with DIL (DIP)
switches, where the device address and the serial interface mode can be selected. Be-
sides this configuration option, Beijer Electronics RBCs allow full software configu-
ration, which is stored in an internal flash memory. The software configuration also
includes device address and serial interface mode setting. The value returned with
this command indicates whether the device uses hardware settings selected with the
DIL switches, or software settings stored in the internal memory.

Supported since Firmware Version
LAUER RBC: 0.0.0.1

Command Stream

Response Message (Acknowledge)

Response Message (Negative Acknowledge)
Under normal operation conditions, a device never sends a negative acknowledge in
response to this command.

Maximum Lr for this Command
9

Example
Check, whether the device at address 0.7 (group 0, address 7) overrides the DIL set-
tings (i.e. device address and serial interface mode):

According to the data returned by the device at address 0.7 (group 0, address 7), the
device uses DIL settings:

0

1

2

3

4

5

6

7...8

9

0x07

ADR

0x4C

0x41

0x55

0x02

ICHKH 0x01

0x0E

ICHKD

0

1

2

3

4

5

6

7

8

0x06

ADR

0x4C

0x41

0x55

0x01

ICHKH

Ret

ICHKD

Ret

Value:

0x00: Device is configured to use the DIL switch settings
0x01: Device is configured to use the software settings

Type:

Byte

Length:

1

Description: Indicates whether the device should the DIL switch settings

0

1

2

3

4

5

6

7...8

9

0x07

0x07

0x4C

0x41

0x55

0x02

0x0D

0x01

0x0E

0xF0

0

1

2

3

4

5

6

7

8

0x06

0x07

0x4C

0x41

0x55

0x01

0x0F

0x00

0xFF