3.7. Guidelines for mounting (IP55/IP66 Units) 

Before mounting the drive, ensure that the chosen location meets the environmental condition requirements for the drive shown in 
section 10.1 

The drive must be mounted vertically, on a suitable flat surface 

The minimum mounting clearances as shown in the table below must be observed 

The mounting site and chosen mountings should be sufficient to support the weight of the drives 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Drive 

Size 

X  

Above & Below 

Either Side 

 

mm 

mm 

2 (IP66) 

200 

10 

3 (IP66) 

200 

10 

4 (IP55) 

200 

10 

5 (IP55) 

200 

10 

6 (IP55) 

200 

10 

7 (IP55) 

200 

10 

Note : 

Typical drive heat losses are 3% of operating load 
conditions. 
 
Above are guidelines only and the operating ambient 
temperature of the drive MUST be maintained at all 
times. 

Cable Gland Sizes

Drive 

size 

Power 

Cable 

Motor 

Cable 

Control 

Cables 

M25 (PG21) 

M25 (PG21) 

M20 (PG13.5) 

M25 (PG21) 

M25 (PG21) 

M20 (PG13.5) 

M32 (PG29) 

M32 (PG29) 

M20 (PG13.5) 

M50 (PG36) 

M50 (PG36) 

M20 (PG13.5) 

6 and 7 

No predrilled glandholes 

 

Using the drive as a template, or the dimensions shown above, mark the locations required for drilling 

Suitable cable glands to maintain the IP protection of the drive are required. Gland sizes should be selected based on the number and 
size of the required connection cables. Drives are supplied with either predrilled holes or a plain, undrilled gland plate to allow the 
correct hole sizes to be cut as required. Remove the gland plate from the drive prior to drilling.  

 