Parameters, Parameter set overview, Parameter group 1 – basic parameters – Beijer Electronics BFI-P2 V1.21 User Manual

Page 33

Advertising
background image

User Guide Revision 1.121 

 

www.beijerelectronics.com 

33 

6. Parameters 

6.1. Parameter Set Overview 

The Parameter set consists of 6 groups as follows: 

Group 0 – Read Only Monitoring Parameters 

Group 1 – Basic Configuration Parameters 

Group 2 – Extended Parameters 

Group 3 – PID Control Parameters 

Group 4 – High Performance Motor Control Parameters 

Group 5 –Field Bus Parameters 

 
When the Drive is reset to factory defaults, or is in its factory supplied state, only Group 1 Parameters can be accessed. In order to allow access 
to parameters from the higher level groups, P1‐14 must be set to the same value as P2‐40 (Default setting = 101). With this setting, parameter 
groups 1 – 5 can be accessed, along with the first 38 parameters in Group 0. 

6.2. Parameter Group 1 – Basic Parameters 

Par 

Parameter Name 

Minimum 

Maximum 

Default 

Units 

P1‐01 

Maximum Frequency / Speed Limit 

P1‐02 

500.0 

50.0 (60.0) 

Hz / Rpm 

Maximum output frequency or motor speed limit – Hz or rpm. 
If P1‐10 >0, the value entered / displayed is in Rpm 

P1‐02 

Minimum Frequency / Speed Limit 

0.0 

P1‐01 

0.0 

Hz / Rpm 

Minimum speed limit – Hz or rpm. 
If P1‐10 >0, the value entered / displayed is in Rpm 

P1‐03 

Acceleration Ramp Time 

See Below 

5.0 / 10.0 

Seconds 

Acceleration ramp time from 0 to base speed (P‐1‐09) in seconds. 

Note 

FS2 & FS3 : 5.0 Seconds Default Setting, 0.01 Seconds Resolution, 600.0 Seconds Maximum 
FS4 – FS7 : 10.0 Seconds Default Setting, 0.1 Seconds Resolution, 6000 Seconds Maximum 

P1‐04 

Deceleration Ramp Time 

See Below 

5.0 / 10.0 

Seconds 

Deceleration ramp time from base speed (P1‐09) to standstill in seconds.  When set to zero, fastest possible ramp time without trip is 
activated 

Note 

FS2 & FS3 : 5.0 Seconds Default Setting, 0.01 Seconds Resolution, 600.0 Seconds Maximum 
FS4 – FS7 : 10.0 Seconds Default Setting, 0.1 Seconds Resolution, 6000.0 Seconds Maximum 

P1‐05 

Stop Mode 

‐ 

0 : Ramp To Stop. When the enable signal is removed, the drive will ramp to stop, with the rate controlled by P1‐04 as described 
above. In this mode, the drive brake transistor (where fitted) is disabled. 
1 : Coast to Stop. When the enable signal is removed, the drive output is immediately disabled, and the motor will coast (freewheel) 
to stop. If the load can continue to rotate due to inertia, and the drive may possibly be re‐enabled whilst the motor is still rotating, 
the spin start function (P2‐26) should be enabled. In this mode, the drive brake transistor (where fitted) is disabled. 
2 : Ramp To Stop. When the enable signal is removed, the drive will ramp to stop, with the rate controlled by P1‐04 as described 
above. The Drive Brake chopper is also enabled in this mode. 
3 : Coast to Stop. When the enable signal is removed, the drive output is immediately disabled, and the motor will coast (freewheel) 
to stop. If the load can continue to rotate due to inertia, and the drive may possibly be re‐enabled whilst the motor is still rotating, 
the spin start function (P2‐26) should be enabled. The drive brake chopper is enabled in this mode, however it will only activate when 
required during a change in the drive frequency setpoint, and will not activate when stopping. 

P1‐06 

Energy Optimiser 

‐ 

Only active when enhanced V/F motor control mode is selected (P4‐01 = 2). 
0 : Disabled 
1 : Enabled. When enabled, the Energy Optimiser attempts to reduce the overall energy consumed by the drive and motor when 
operating at constant speeds and light loads. The output voltage applied to the motor is reduced. The Energy Optimiser is intended 
for applications where the drive may operate for some periods of time with constant speed and light motor load, whether constant or 
variable torque. 

P1‐07 

Motor Rated Voltage 

Drive Rating Dependent 

Volts 

This parameter should be set to the rated (nameplate) voltage of the motor (Volts) 

P1‐08 

Motor Rated Current 

Drive Rating Dependent 

Amps 

This parameter should be set to the rated (nameplate) current of the motor 

P1‐09 

Motor Rated Frequency 

10 

500 

50 (60) 

Hz 

This parameter should be set to the rated (nameplate) frequency of the motor 

P1‐10 

Motor Rated Speed 

30000 

Rpm 

This parameter can optionally be set to the rated (nameplate) rpm of the motor. When set to the default value of zero, all speed 
related parameters are displayed in Hz, and the slip compensation for the motor is disabled. Entering the value from the motor 
nameplate enables the slip compensation function, and the Drive display will now show motor speed in estimated rpm. All speed 
related parameters, such as Minimum and Maximum Speed, Preset Speeds etc. will also be displayed in Rpm. 
Note : When the drive is operated with the optional Encoder Feedback Interface, this parameter must be set to the correct 
nameplate Rpm of the connected motor. 