4.1.2. Grounding Guidelines 

The ground terminal of each Drive should be individually connected DIRECTLY to the site ground bus bar (through the filter if installed). Drive 
ground connections should not loop from one drive to another, or to, or from any other equipment. Ground loop impedance must confirm to 
local industrial safety regulations. To meet UL regulations, UL approved ring crimp terminals should be used for all ground wiring connections.  
The drive Safety Ground must be connected to system ground. Ground impedance must conform to the requirements of national and local 
industrial safety regulations and/or electrical codes. The integrity of all ground connections should be checked periodically. 

4.1.3. Protective Earth Conductor 

The Cross sectional area of the PE Conductor must be at least equal to that of the incoming supply conductor. 

4.1.4. Safety Ground 

 

This is the safety ground for the drive that is required by code. One of these points must be connected to adjacent building steel (girder, joist), a 
floor ground rod, or bus bar. Grounding points must comply with national and local industrial safety regulations and/or electrical codes.  

4.1.5. Motor Ground 

The motor ground must be connected to one of the ground terminals on the drive.  

4.1.6. Ground Fault Monitoring 

As with all inverters, a leakage current to earth can exist. The Drive is designed to produce the minimum possible leakage current whilst 
complying with worldwide standards. The level of current is affected by motor cable length and type, the effective switching frequency, the 
earth connections used and the type of RFI filter installed. If an ELCB (Earth Leakage Circuit Breaker) is to be used, the following conditions apply: 
‐ 

A Type B Device must be used 

The device must be suitable for protecting equipment with a DC component in the leakage current  

Individual ELCBs should be used for each Drive 

4.1.7. Shield Termination (Cable Screen) 

The safety ground terminal provides a grounding point for the motor cable shield. The motor cable shield connected to this terminal (drive end) 
should also be connected to the motor frame (motor end). Use a shield terminating or EMI clamp to connect the shield to the safety ground 
terminal.  

4.2. Wiring Precautions 

Connect the Drive according to section 4.3, ensuring that motor terminal box connections are correct. There are two connections in general: Star 
and Delta. It is essential to ensure that the motor is connected in accordance with the voltage at which it will be operated. For more information, 
refer to section 4.6 Motor Terminal Box Connections.  
 
It is recommended that the power cabling should be 4‐core PVC‐insulated screened cable, laid in accordance with local industrial regulations and 
codes of practice. 

4.3. Incoming Power Connection 

For 1 phase supply, power should be connected to L1/L, L2/N. 

For 3 phase supplies, power should be connected to L1, L2, and L3.  Phase sequence is not important. 

For compliance with CE and C Tick EMC requirements, a symmetrical shielded cable is recommended. 

A fixed installation is required according to IEC61800‐5‐1 with a suitable disconnecting device installed between the Drive and the AC 
Power Source. The disconnecting device must conform to the local safety code / regulations (e.g. within Europe, EN60204‐1, Safety of 
machinery).  

The cables should be dimensions according to any local codes or regulations. Guideline dimensions are given in section 10.2. 

Suitable fuses to provide wiring protection of the input power cable should be installed in the incoming supply line, according to the 
data in section 10.2. The fuses must comply with any local codes or regulations in place.  In general, type gG (IEC 60269) or UL type T 
fuses are suitable; however in some cases type aR fuses may be required. The operating time of the fuses must be below 0.5 seconds. 

Where allowed by local regulations, suitably dimensioned type B MCB circuit breakers of equivalent rating may be utilised in place of 
fuses, providing that the clearing capacity is sufficient for the installation.  

When the power supply is removed from the drive, a minimum of 30 seconds should be allowed before re‐applying the power. A 
minimum of 5 minutes should be allowed before removing the terminal covers or connection. 

The maximum permissible short circuit current at the Drive Power terminals as defined in IEC60439‐1 is 100kA. 

An optional Input Choke is recommended to be installed in the supply line for drives where any of the following conditions occur:‐ 

o

The incoming supply impedance is low or the fault level / short circuit current is high 

o

The supply is prone to dips or brown outs 

o

An imbalance exists on the supply (3 phase drives) 

o

The power supply to the drive is via a bus bar and brush gear system (typically overhead Cranes). 

In all other installations, an input choke is recommended to ensure protection of the drive against power supply faults. Contact Beijer 
Electronics for further information. 

 
 
 
 
 