Troubleshooting – Beijer Electronics BFI-P2 V1.21 User Manual

Page 52

Advertising
background image

User Guide Revision 1.12 

 

www.beijerelectronics.com 

52

 
 

11. Troubleshooting 

Fault Code 

No. 

Description 

Corrective Action

no-Flt

00 

No Fault 

Displayed in P0‐13 if no faults are recorded in the log 

OI-b

01 

Brake channel over current 

Ensure the connected brake resistor is above the minimum permissible level for the drive –
refer to the ratings shown in section 10.2.  
Check the brake resistor and wiring for possible short circuits.  

OL-br

02 

Brake resistor overload 

The drive software has determined that the brake resistor is overloaded, and trips to protect 
the resistor. Always ensure the brake resistor is being operated within its designed parameter 
before making any parameter or system changes. 
To reduce the load on the resistor, increase deceleration the time, reduce the load inertia or 
add further brake resistors in parallel, observing the minimum resistance value for the drive 
in use. 

O-I

03 

Instantaneous over current on drive 
output.  
Excess load on the motor. 

Fault Occurs on Drive Enable
Check the motor and motor connection cable for phase – phase and phase – earth short 
circuits. 
Check the load mechanically for a jam, blockage or stalled condition 
Ensure the motor nameplate parameters are correctly entered, P1‐07, P1‐08, P1‐09. 
If operating in Vector mode (P4‐01 – 0 or 1), also check the motor power factor in P4‐05 and 
ensure an autotune has been successfully completed for the connected motor. 
Reduced the Boost voltage setting in P1‐11 
Increase the ramp up time in P1‐03 
If the connected motor has a holding brake, ensure the brake is correctly connected and 
controlled, and is releasing correctly 
Fault Occurs When Running 
If operating in Vector mode (P4‐01 – 0 or 1), reduce the speed loop gain in P4‐03 

I.t-trp

04 

Drive has tripped on overload after 
delivering >100% of value in P1‐08 for 
a period of time. 

Check to see when the decimal points are flashing (drive in overload) and either increase 
acceleration rate or reduce the load.  
Check motor cable length is within the limit specified for the relevant drive in section 10.2 
 Ensure the motor nameplate parameters are correctly entered in P1‐07, P1‐08, and P1‐09 
If operating in Vector mode (P4‐01 – 0 or 1), also check the motor power factor in P4‐05 and 
ensure an autotune has been successfully completed for the connected motor.  
Check the load mechanically to ensure it is free, and that no jams, blockages or other 
mechanical faults exist 

PS-trP

05 

Hardware Over Current  

Check the wiring to motor and the motor for phase to phase and phase to earth short 
circuits. Disconnect the motor and motor cable and retest. If the drive trips with no motor 
connected, it must be replaced and the system fully checked and retested before a 
replacement unit is installed. 

O-Volt

06 

Over voltage on DC bus 

The value of the DC Bus Voltage can be displayed in P0‐20 
A historical log is stored at 256ms intervals prior to a trip in parameter P0‐36 
This fault is generally caused by excessive regenerative energy being transferred from the 
load back to the drive. When a high inertia or over hauling type load is connected. 
If the fault occurs on stopping or during deceleration, increase the deceleration ramp time 
P1‐04 or connect a suitable brake resistor to the drive. 
If operating in Vector Mode, reduce the speed loop gain P4‐03 
If operating in PID control, ensure that ramps are active by reducing P3‐11 

U-Volt

07 

Under voltage on DC bus 

This occurs routinely when power is switched off. 
If it occurs during running, check the incoming supply voltage, and all connections into the 
drive, fuses, contactors etc. 

O-t

08 

Heatsink over temperature 

The heatsink temperature can be displayed in P0‐21. 
A historical log is stored at 30 second intervals prior to a trip in parameter P0‐38 
Check the drive ambient temperature 
Ensure the drive internal cooling fan is operating 
Ensure that the required space around the drive as shown in sections 3.5 to 3.8has been 
observed, and that the cooling airflow path to and from the drive is not restricted 
Reduce the effective switching frequency setting in parameter P2‐24 
Reduce the load on the motor / drive 

U-t

09 

Under temperature

Trip occurs when ambient temperature is less than ‐10°C.  The temperature must be raised 
over ‐10°C in order to start the drive. 

P-def

10 

Factory Default parameters have 
been loaded 

Press STOP key, the drive is now ready to be configured for the required application

E-trip

11 

External trip 

E‐trip requested on control input terminals. Some settings of P1‐13 require a normally closed 
contactor to provide an external means of tripping the drive in the event that an external 
device develops a fault. If a motor thermistor is connected check if the motor is too hot. 

SC-Obs

12 

Communications Fault 

Communications lost with PC or remote keypad. Check the cables and connections to 
external devices 

Flt-dc

13 

Excessive DC Ripple

The DC Bus Ripple Voltage level can be displayed in parameter P0‐22 
A historical log is stored at 20ms  intervals prior to a trip in parameter P0‐39 
Check all three supply phases are present and within the 3% supply voltage level imbalance 
tolerance. 
Reduce the motor load, If the fault persists, contact your local distributor or Sales Partner 

P-Loss

14 

Input phase loss trip 

Drive intended for use with a 3 phase supply, one input phase has been disconnected or lost.