8.2. Parameter Group 3 – PID Control 

Par 

Parameter Name 

Minimum 

Maximum 

Default 

Units 

P3‐01 

PID Proportional Gain 

0.1 

30.0 

1.0 

‐ 

PID Controller Proportional Gain. Higher values provide a greater change in the drive output frequency in response to small changes 
in the feedback signal. Too high a value can cause instability 

P3‐02 

PID Integral Time Constant 

0.0 

30.0 

1.0 

PID Controller Integral Time. Larger values provide a more damped response for systems where the overall process responds slowly 

P3‐03 

PID Differential Time Constant 

0.00 

1.00 

0.00 

PID Differential Time Constant 

P3‐04 

PID Operating Mode 

‐ 

0 : Direct Operation. Use this mode if an increase in the motor speed should result in an increase in the feedback signal 
1 : Inverse Operation. Use this mode if an increase in the motor speed should result in a decrease in the feedback signal 

P3‐05 

PID Reference (Setpoint) Source Select 

‐ 

Selects the source for the PID Reference / Setpoint 
0 : Digital Preset Setpoint. P3‐06 is used 
1 : Analog Input 1 Setpoint 
2 :  Analog Input 2 Setpoint 

P3‐06 

PID Digital Reference (Setpoint) 

0.0 

100.0 

0.0 

When P3‐05 = 0, this parameter sets the preset digital reference (setpoint) used for the PID Controller 

P3‐07 

PID Controller Output Upper Limit 

P3‐08 

100.0 

100.0 

Limits the maximum value output from the PID controller 

P3‐08 

PID Controller Output Lower Limit 

0.0 

P3‐07 

0.0 

Limits the minimum output from the PID controller 

P3‐09 

PID Output Limit Control 

‐ 

0 : Digital Output Limits. The output range of the PID controller is limited by the values of P3‐07 & P3‐08 
1 : Analog Input 1 Provides a Variable Upper Limit. The output range of the PID controller is limited by the values of P3‐08 & the 
signal applied to Analog Input 1 
2:  Analog Input 1 Provides a Variable Lower Limit. The output range of the PID controller is limited by the signal applied to Analog 
Input 1 & the value of P3‐07 
3: PID output Added to Analog Input 1 Value. The output value from the PID Controller is added to the speed reference applied to 
the Analog Input 1 

P3‐10 

PID Feedback Signal Source Select 

‐ 

0 : Analog Input 2 
1 : Analog Input 1 
2 : Output Current 
3 : DC Bus Voltage 
4 : Differential : Analog Input 1 – Analog Input 2 
5 : Largest Value : Analog Input 1 or Analog Input 2
 

P3‐11 

Maximum PID Error to Enable Ramps 

0.0 

25.0 

0.0 

Defines a threshold PID error level, whereby if the difference between the setpoint and feedback values is less than the set threshold, 
the internal ramp times of the drive are disabled. Where a greater PID error exists, the ramp times are enabled to limit the rate of 
change of motor speed on large PID errors, and react quickly to small errors. 
Setting to 0.0 means that the drive ramps are always enabled. This parameter is intended to allow the user to disable the drive 
internal ramps where a fast reaction to the PID control is required, however by only disabling the ramps when a small PID error exists, 
the risk of possible over current or over voltage trips being generated are reduced. 

P3‐12 

PID Feedback Value Display Scaling Factor 

0.000 

50.000 

0.000 

‐ 

Applies a scaling factor to the displayed PID feedback, allowing the user to display the actual signal level from a transducer, e.g. 0 – 10 
Bar etc. 

P3‐13 

PID Feedback Wake Up Level 

0.0 

100.0 

0.0 

Sets a programmable level whereby if the drive enters standby motor whilst operating under PID control, the selected feedback signal 
must fall below this threshold before the drive will return to normal operation. 

P3‐18 

PID Operation Control 

‐ 

‐ 

‐ 

‐ 

0 : Continuous PID Operation. In this operating mode, the PID controller operates continuously, regardless of whether the drive is 
enabled or disabled. This can result in the output of the PID controller reaching the maximum level prior to the drive enable signal 
being applied. 
1 : PID operation on Drive Enable.In this operating mode, the PID controller only operates when the drive is enabled, and hence will 
always start from zero when the drive is enabled. 