53 

Fault Code 

No. 

Description 

Corrective Action

h O-I

15 

Instantaneous over current on drive 
output.  

Refer to fault 3 above

th-Flt

16 

Faulty thermistor on heatsink. 

Refer to your local distributor or Sales Partner.

data-F

17 

Internal memory fault. 

Parameters not saved, defaults reloaded.
Try again. If problem recurs, refer to your Beijer Authorised Distributor. 

4-20F

18 

4‐20mA Signal Lost

The reference signal on Analog Input 1 or 2 (Terminals 6 or 10) has dropped below the 
minimum threshold of 3mA. Check the signal source and wiring to the The drive terminals. 

data-E

19 

Internal memory fault. 

Parameters not saved, defaults reloaded.
Try again. If problem recurs, refer to your Beijer Authorised Distributor. 

U-Def

20 

User Parameter Defaults 

User Parameter defaults have been loaded. Press the Stop key. 

F-Ptc

21 

Motor PTC Over Temperature 

The connected motor PTC device has caused the drive to trip 

FaN-F

22 

Cooling Fan Fault

Check and if necessary, replace the drive internal cooling fan 

O-heat

23 

Ambient Temperature too High 

The measured temperature around the drive is above the operating limit of the drive.
Ensure the drive internal cooling fan is operating 
Ensure that the required space around the drive as shown in sections 3.5 to 3.8 has been 
observed, and that the cooling airflow path to and from the drive is not restricted 
Increase the cooling airflow to the drive 
Reduce the effective switching frequency setting in parameter P2‐24 
Reduce the load on the motor / drive 

O-torq

24 

Maximum Torque Limit Exceeded 

The output torque limit has exceeded the drive capacity or trip threshold
Reduce the motor load, or increase the acceleration time 

U-Torq

25 

Output Torque Too Low 

Active only when hoist brake control is enabled P2‐18 = 8. The torque developed prior to 
releasing the motor holding brake is below the preset threshold. 

Out-F

26 

Drive output fault

Drive output fault

Sto-F

29 

Internal STO circuit Error  

Safety input circuit error.

Enc-01

30 

Encoder Feedback Faults 
(Only visible when an encoder 
module is fitted and enabled) 

Encoder communication /data loss

Enc-02

31 

Encoder Speed Error. The error between the measured encoder feedback speed and the The 
drive estimated rotor speed is greater than the pre‐set limit allowed. 

Enc-03

32 

Incorrect Encoder PPR count set in parameters

Enc-04

33 

Encoder Channel A Fault

Enc-05

34 

Encoder Channel B Fault

Enc-06

35 

Encoder Channels A & B Fault

AtF-01

40 

Autotune Failed 

Measured motor stator resistance varies between phases. Ensure the motor is correctly 
connected and free from faults.  Check the windings for correct resistance and balance. 

AtF-02

41 

Measured motor stator resistance is too large. Ensure the motor is correctly connected and 
free from faults. Check that the power rating corresponds to the power rating of the 
connected drive. 

AtF-03

42 

Measured motor inductance is too low. Ensure the motor is correctly connected and free 
from faults. 

AtF-04

43 

Measured motor inductance is too large. Ensure the motor is correctly connected and free 
from faults. Check that the power rating corresponds to the power rating of the connected 
drive. 

AtF-05

44 

Measured motor parameters are not convergent. Ensure the motor is correctly connected 
and free from faults. Check that the power rating corresponds to the power rating of the 
connected drive. 

Out-Ph

49 

Output (Motor) Phase Loss 

One of the motor output phases is not connected to the drive. 

Sc-F01

50 

Modbus comms fault 

A valid Modbus telegram has not been received within the watchdog time limit set in P5‐05
Check the network master / PLC is still operating 
Check the connection cables 
Increase the value of P5‐05 to a suitable level 

Sc-F02

51 

CAN Open comms trip 

A valid CAN open telegram has not been received within the watchdog time limit set in P5‐05
Check the network master / PLC is still operating 
Check the connection cables 
Increase the value of P5‐05 to a suitable level 

Sc-F03

52 

Communications Option Module 
Fault 

Internal communication to the inserted Communication Option Module has been lost.
Check the module is correctly inserted 

Sc-F04

53 

IO card comms trip

Internal communication to the inserted Option Module has been lost. 
Check the module is correctly inserted 

 