Technical data, Environmental, Input / output power and current ratings – Beijer Electronics BFI-P2 V1.21 User Manual

Page 48

Advertising
background image

User Guide Revision 1.12 

 

www.beijerelectronics.com 

48

 
10. Technical Data 

10.1. Environmental 

Ambient temperature range  Operational 

: ‐10 … 50 °C (IP20 Units), 40°C (IP55 Units), 30°C (IP55, 90kW / 150HP units) 

 

 

 

Storage   

: ‐40 °C … 60 °C 

Max altitude for rated operation 

 

: 1000m 

Derating above 1000m (to 4000m max)  

: 1% / 100m 

Relative Humidity   

 

 

: < 95% (non condensing) 

Note  

:  

Drive must be Frost and moisture free at all times 

 

 

Installation above 2000m is not UL approved 

10.2. Input / Output Power and Current ratings 

The following tables provide the output current rating information for the various drivemodels. It is always recommend that the selection of the 
correct drive is based upon the motor full load current at the incoming supply voltage. 

200 ‐ 240 Volt (+ / ‐ 10%) 1 Phase Input, 3 Phase Output 

kW 

HP 

Nominal 

Fuse 

Supply 

Nominal 

Motor 

Maximum 

Recommended 

 

 

Input 

Or 

Cable 

Output 

Cable 

Motor 

Brake 

 

 

Current 

MCB (Type B) 

Size 

Current 

Size 

Cable 

Resistance 

 

 

 

Non UL 

UL 

mm 

AWG / kcmil 

 

mm 

AWG 

Length 

Ω 

0.75 

10.5 

16 

15 

2.5 

12 

4.3 

1.5 

14 

100 

100 

1.5 

16.2 

20 

20 

10 

1.5 

14 

100 

50 

2.2 

23.8 

25 

25 

10 

10.5 

1.5 

14 

100 

35 

 

Note 

• Ratings shown above apply to 40°C Ambient temperature. For derating information, refer to section 10.4 
• The maximum motor cable length stated applies to using a shielded motor cable. When using an unshielded cable, the maximum cable length 

limit may be increased by 50%. When using the recommended output choke, the maximum cable length may be increased by 100% 

• The PWM output switching from any inverter when used with a long motor cable length can cause an increase in the voltage at the motor 

terminals, depending on the motor cable length and inductance. The rise time and peak voltage can affect the service life of the motor Beijer 
Electronics recommend using an output choke for motor cable lengths of 50m or more to ensure good motor service life 

• For UL compliant installation, use Copper wire with a minimum insulation temperature rating of 70°C, UL Class CC or Class J Fuses 

200 ‐ 240 Volt (+ / ‐ 10%) 3 Phase Input, 3 Phase Output 

kW 

HP 

Nominal 

Fuse 

Supply 

Nominal 

Motor 

Maximum 

Recommended 

 

 

Input 

Or 

Cable 

Output 

Cable 

Motor 

Brake 

 

 

Current 

MCB (Type B) 

Size 

Current 

Size 

Cable 

Resistance 

 

 

 

Non UL 

UL (A) 

mm 

AWG / kcmil 

 

mm 

AWG / kcmil 

Length 

Ω 

0.75 

3.7 

10 

1.5 

14 

4.3 

1.5 

14 

100 

100 

1.5 

5.9 

10 

10 

1.5 

14 

1.5 

14 

100 

50 

2.2 

7.9 

10 

10 

1.5 

14 

10.5 

1.5 

14 

100 

35 

16.3 

25 

25 

10 

18 

2.5 

10 

100 

20 

5.5 

7.5 

22.5 

32 

30 

10 

24 

10 

100 

20 

7.5 

10 

32.9 

50 

45 

16 

30 

100 

22 

11 

15 

54.1 

80 

70 

25 

46 

10 

100 

22 

15 

20 

69.6 

100 

90 

35 

61 

16 

100 

12 

18.5 

25 

76.9 

100 

100 

35 

72 

25 

100 

12 

22 

30 

92.3 

125 

125 

50 

90 

35 

100 

30 

40 

116.9 

160 

150 

70 

1/0 

110 

50 

1/0 

100 

37 

50 

150.2 

200 

200 

95 

3/0 

150 

70 

3/0 

100 

45 

60 

176.5 

250 

225 

120 

4/

0

180 

95 

4/0 

100 

55 

75 

211 

300 

300 

185 

300 

202 

120 

250 

100 

75 

120 

267 

400 

350 

2 x 95 

400 

248 

150 

350 

100 

 

Note 

• Ratings shown above apply to 40°C Ambient temperature. For derating information, refer to section 10.4 
• The maximum motor cable length stated applies to using a shielded motor cable. When using an unshielded cable, the maximum cable length 

limit may be increased by 50%. When using the recommended output choke, the maximum cable length may be increased by 100% 

• The PWM output switching from any inverter when used with a long motor cable length can cause an increase in the voltage at the motor 

terminals, depending on the motor cable length and inductance. The rise time and peak voltage can affect the service life of the motor. Beijer 
Electronics recommend using an output choke for motor cable lengths of 50m or more to ensure good motor service life 

• For UL compliant installation, use Copper wire with a minimum insulation temperature rating of 70°C, UL Class CC or Class J Fuses 