4.10.7. “STO“Electrical Installation 

 
The “STO” wiring shall be protected from inadvertent short circuits or tampering which could lead to failure of the “STO” input signal, 
further guidance is given in the diagrams below. 
 

In addition to the wiring guidelines for the “STO” circuit below, section 4.1.1 “Recommended installation for EMC compliance. should also be 
followed. 
 
The drive should be wired as illustrated below; the 24Vdc signal source applied to the “STO” input can be either from the 24Vdc on the drive or 
from an External 24Vdc power supply. 
 

4.10.7.1.

Recommended “STO” wiring 

Using an External 24Vdc Power Supply.  

 

                      Using the drives on‐board 24Vdc supply 

         

‐ Twisted‐Pair 
‐ Shielded cables

1213

0V

+24Vdc

Safety relay

Protective Capped Trunking 
or equivalent to prevent 
STO Cable short circuit to an 
external Voltage source.

External  

Power 

Supply

            

 

       

                                  

 

                                      Note : The Maximum cable length from Voltage source to the drive terminals should not exceed 25 mtrs. 

4.10.8. External Power supply Specification. 

Voltage Rating (Nominal) 

24Vdc 

STO Logic High 

18‐30Vdc (Safe torque off in standby) 

Current Consumption (Maximum) 

100mA  

4.10.9. Safety Relay Specification. 

The safety relay should be chosen so that at minimum it meets the safety standards in which the drive meets. 

Standard Requirements 

SIL2 or PLd SC3 or better (With Forcibly guided Contacts)  

Number of Output Contacts 

2 independent  

Switching Voltage Rating 

30Vdc 

Switching Current 

100mA 

Wires should be 
protected 
against short 
circuits as 
shown above 