380 ‐ 480 Volt (+ / ‐ 10%) 3 Phase Input, 3 Phase Output 

kW 

HP 

Nominal 

Fuse 

Supply 

Nominal 

Motor 

Maximum 

Recommended 

(400V) 

(460V) 

Input 

Or 

Cable 

Output 

Cable 

Motor 

Brake 

 

 

Current 

MCB (Type B) 

Size 

Current 

Size 

Cable 

Resistance 

 

 

 

Non 

UL 

UL (A) 

mm 

AWG / 

kcmil 

 

mm 

AWG / 

kcmil 

Length 

Ω 

0.75 

10 

1.5 

14 

2.2 

1.5 

14 

100 

400 

1.5 

5.1 

10 

10 

1.5 

14 

4.1 

1.5 

14 

100 

200 

2.2 

7.7 

10 

10 

1.5 

14 

5.8 

1.5 

14 

100 

150 

11.7 

16 

15 

2.5 

14 

9.5 

1.5 

14 

100 

100 

5.5 

7.5 

14.1 

20 

20 

12 

14 

1.5 

12 

100 

75 

7.5 

10 

18.3 

25 

25 

10 

18 

2.5 

10 

100 

50 

11 

15 

27 

40 

35 

10 

24 

10 

100 

40 

15 

20 

29 

40 

40 

10 

30 

100 

22 

18.5 

25 

39.7 

50 

50 

16 

39 

10 

100 

22 

22 

30 

48.6 

63 

70 

16 

46 

10 

100 

22 

30 

40 

61.5 

80 

80 

25 

61 

16 

100 

12 

37 

50 

72.3 

100 

100 

35 

72 

25 

100 

12 

45 

60 

91.2 

125 

125 

50 

90 

35 

100 

55 

75 

116.9 

160 

150 

70 

1/0 

110 

50 

1/

0

100 

75 

100 

150.2 

200 

200 

95 

3/0 

150 

70 

3/

0

100 

90 

150 

176.5 

250 

225 

120 

4/

0

180 

95 

4/0 

100 

110 

175 

217.2 

300 

300 

185 

300 

202 

120 

250 

100 

132 

200 

255.7 

400 

350 

2 x 95 

400 

240 

150 

350 

100 

160 

200 

302.4 

400 

400 

2 x 95 

500 

302 

2 x 70 

500 

100 

200 

200 

370 

500 

500 

2 x 150 

750 

370 

2 x 95 

750 

100 

250 

200 

450 

600 

600 

2 x 150 

1250 

450 

2 x 120 

1250 

100 

 

 

Note 

• Ratings shown above apply to 40°C Ambient temperature. For derating information, refer to section 1Error! Reference source not found..4 
• The maximum motor cable length stated applies to using a shielded motor cable. When using an unshielded cable, the maximum cable length 

limit may be increased by 50%. When using recommended output choke, the maximum cable length may be increased by 100% 

• The PWM output switching from any inverter when used with a long motor cable length can cause an increase in the voltage at the motor 

terminals, depending on the motor cable length and inductance. The rise time and peak voltage can affect the service life of the motor. Beijer 
Electronics recommend using an output choke for motor cable lengths of 50m or more to ensure good motor service life 

• For UL compliant installation, use Copper wire with a minimum insulation temperature rating of 70°C, UL Class CC or Class J Fuses 