Operating Instructions Temperature Indicating Controller CF2S

V1.2

08/2004 - 16 -

Alarm 1 (A1) setting

Mode to set the action point of the Alarm 1 (A1) output.

Setting value

This item is not displayed if setting the rotary switch
to No. 0 or No. 7 (See page 12.)
Setting range: see [table 4.2-2].

[Factory adjusted as 0°C]

Alarm 2 (A2) setting

Mode to set the action point of the Alarm 2 (A2) output.

Setting value

This item is not displayed if the option [A2] is not
applied or even if it is applied, when setting the
rotary switch to No. 0 or No. 7 (See page 12.)
Setting range: see [table 4.2-2].

[Factory adjusted as 0°C]

Setting range of Alarm 1 and 2
(The setting range is the same when the standby function is added.)

[Table 4.2-2]

Alarm type

Setting range

High limit alarm

–Input span to Input span

Low limit alarm

–Input span to Input span

High/Low limits alarm

1 to Input span

High/Low limit range alarm

1 to Input span

Process high alarm

Input range minimum to Input range maximum

Process low alarm

Input range minimum to Input range maximum

For RTD input, the minimum value of the negative side is –199.9.

Loop break alarm

Mode to set the time for Loop break alarm

time setting

activation assessment.

Setting value Setting range: 0 to 200 minutes

[Factory adjusted as 0 minutes.]

This display is indicated only when the option [AR] or
[AL] is applied.

Loop break alarm

Mode to set the span for Loop Break Alarm

span setting

activation assessment.

Setting value Setting range:

0 to 150°C (Thermocouple, except T and RTD

without a decimal point)

0.0 to 150.0°C (Thermocouple T and RTD

with a decimal point)

[Factory adjusted as 0°C]
This display is indicated only when the option [AR] or
[AL] is applied.

PV/SV display mode

Actual Main setting
Temperature value