Operating Instructions Temperature Indicating Controller CF2S

V1.2

08/2004 - 37 -

Notice

• Use a thermocouple and compensating lead wire according to the input

specifications of this controller.

• Use a 3-wire RTD system according to the input specifications of this controller.
• This controller has neither built-in power switch nor fuse. Therefore, it is

necessary to install them in the circuit near the external controller.
(Recommended fuse: Time-lag fuse, rated voltage 250V, rated current 2A)

• In the case of 24Vdc for power source, do not confuse the polarity.
• For the relay contact output type, use an external auxiliary electromagnetic

switch to protect the built-in relay contact.

• When wiring, keep the input wire (Thermocouple, RTD, etc.) away from AC

source and the load wire to avoid external interference.

• Use a thick wire (1.25 to 2.0mm²) for the earth ground.

n Solderless terminal

Use a solderless terminal with an insulation sleeve that fits to an M3 screw as shown

below.