Operating Instructions Temperature Indicating Controller CF2S

V1.2

08/2004 - 18 -

Main setting value

Mode to set the high limit of main setting value.

high limit setting

(If scaling high limit value is changed,

Setting value this setting value will be changed as well.)

Setting range: Main setting value low limit to scaling high limit value
[Factory adjusted as 400°C]

Main setting value

Mode to set the low limit of main setting value.

low limit setting

(If scaling low limit value is changed,

Setting value

this setting value will be changed as well.)

Setting range: Scaling low limit value to main setting value high limit
[Factory adjusted as 0°C]

Sensor correction setting

Mode to set the correct value of the sensor.

Setting value Setting range: –100.0 to 100.0°C

[Factory adjusted as 0.0°C]

Instrument number setting

Mode to set the Instrument number individually

Setting value

to each instrument when communicating by
connecting multiple instruments in serial communication.

Setting range: 0 to 95 [Factory adjusted as 0]
This display is available only when the option
[CR2] or [CR5] is applied.

Transfer rate selection

Mode to select a communication transfer rate

Selection

to meet the rate of the host computer.
[Factory adjusted as 9600bps]

2400bps

4800bps

9600bps

19200bps

This display is available only when the option [CR2] or [CR5] is applied.

Communication protocol

Mode to select a communication protocol

selection

between the CF2S and the host computer.

Selection

[Factory adjusted as

]

WIKA standard protocol

Based on Modbus, ASCII mode

This display is available only when the option [CR2] or [CR5] is applied.

PV/SV display mode
Actual Main setting

Temperature

value