Operating Instructions Temperature Indicating Controller CF2S

V1.2

08/2004 - 24 -

(7) Control output OFF function

A function to turn the control output OFF even if the power to the instrument is supplied.
The function is used when required to halt the control action or when the CF2S is not
being used in multiple controllers.
Control output OFF function can be selected from any mode by pressing the

key

for approx. 1 second.
The display is the same as when [Display selection when control output is off] is selected.
(See page 26.)

PV/SV display mode
Actual Main setting
temperature value

for approx. 1s [From any mode, as an example]

Control output OFF function

1s

Manual reset setting

(*) [Unlit]

Setting value

for approx. 1s

(*): PV display indicates [OFF indication], [No indication] or [Only PV]
selected in Display selection when control output is off (page 26).

Notice

Once the Control output OFF function is enabled, the function cannot be released
even if the power to the instrument is turned OFF and turned ON again.
To cancel the function, press the

key again for approx. 1 second.

In the program control, the Control output OFF function cannot be used because
the

key functions as Program Start/Stop key.