12. Specifications

12.1 Standard specifications

Mounting method :

Flush

Setting

: Input system using membrane sheet key

Display

PV display

: Red LED display 4 digits, size: 8(H) x 4(W)mm

SV/MV/TIME display

: Green LED display 4 digits, size: 8(H) x 4(W)mm

Indicating accuracy

Thermocouple input

: Within ±0.3% of input range full scale ±1digit

however, for R or S input, the range 0 to 200°C (400°F), within ±6°C (12°F)

When B input, the range 0 to 300°C (600°F), accuracy is not guaranteed.
When K, J, T input, the range less than 0°C (32°F),
within ±0.5% of full scale ±1digit

(Cold junction compensating accuracy, ±1°C, at 0 to 50°C)

RTD input

: Within ±0.3% of input range full scale ±1digit

Setting accuracy

: The same as indicating accuracy

Input sampling period

: 0.125 seconds

Input

Thermocouple

: K, J, R, S, B, E, T [JIS, IEC], C (W/Re5-26) [ASTM],
N (IEC) and PL-ll (NBS)

External resistance, 100

Ω or less

In the case of input burnout, Upscale

RTD

: Pt100 (JIS, IEC), JPt100, 3-wire system

Allowable input lead wire resistance 10

Ω or less per wire

In the case of input burnout, Upscale

Control output

Relay contact

: 1a

Control capacity, 250Vac 3A (resistive load)

250Vac 1A (inductive load cosø=0.4)

Non-contact voltage

: For SSR drive
12 VDC maximum 40mA DC (short circuit protected)

Current

: 4 to 20mA DC (Isolated type)

Load resistance, maximum 550