Operating Instructions Temperature Indicating Controller CF2S

V1.2

08/2004 - 32 -

8.3 PID auto-tuning of this controller
In order to decide each value of P, I, D and ARW automatically, this system makes the

controlled object’s temperature fluctuate.

(1) When the difference between setting value and processing temperature
is large when the temperature rises.

Fluctuation is applied at the temperature 1.5% of scaling span less than the setting value.

(2) When the control is stable or when control temperature is within ±1.5%
of scaling span.

Fluctuation is applied at the setting value.

(3) When the control temperature is 1.5% or greater of scaling span higher
than the setting value.

Fluctuation is applied at the temperature 1.5% of scaling span higher than the setting value.

1.5% of scaling span

Controlling action is performed

with the values set by PID

auto-tuning.

Setting value

Time

Temperature

[Figure 8.3-1]

Temperature

Setting value

Time

Controlling action is performed

with the values set by PID

auto-tuning.

[Figure 8.3-3]

1.5% of scaling span

Temperature

Setting value

Starting point of auto-tuning

[Figure 8.3-2]

Time

Controlling action is performed

with the values set by PID

auto-tuning.