Operating Instructions Temperature Indicating Controller CF2S

V1.2

08/2004 - 8 -

The following items can be designated by the DIP switch (SW304).
Factory adjusted as all switches OFF [ ].

[Table 3.2-1]

Item

Sw. No.

Designation

Switch status

Fuzzy self-tuning PID action

No.1: OFF

No.2: OFF

PID action

No.1: ON

No.2: OFF

PD action

No.1: OFF

No.2: ON

Control action

1

and

2

ON/OFF action

No.1: ON

No.2: ON

Heating (reverse) action

No.3: OFF

Heating/Cooling
action

3

Cooling (direct) action

No.3: ON

No standby action

No.4: OFF

Alarm 1 (A1)
standby action

4

Standby action

No.4: ON

No standby action

No.5: OFF

Alarm 2 (A2)
standby action

(*1)

5

Standby action

No.5: ON

°C

No.6: OFF

°C/°F

6

°F

No.6: ON

K, J, R, B, N, PL- ,
Pt100, JPt100 (With decimal point)

No.7: OFF

Sensor input

(*2)

7

S, E, T, C,
Pt100 (Without decimal point)

No.7: ON

Manual start

No.8: OFF

Program start
Auto/Manual

8

Automatic start

No.8: ON

*1: The standby function will not work if the option A2 is not applied.
*2: The sensor input can be designated by the combination of this item and the rotary
switch sensor input (SW303). (See page 11.)

Program start: This item is available for the program control.

Manual start : Program starts by pressing the

key.

Automatic start : Set program is automatically started from step 1 by turning the power

supply to the instrument on (after 2 seconds of warm-up status).