Module accessible in three configurations:

Voltage output AN 0-10V

Current output AN 4-20mA

Current output AN 0-20mA



27.2.1. Technical specification

Work modes

4 - 20mA , 0 - 20mA, 0 - 10V

Resolution 16

bit

Current output resistance

<500

Voltage output resistance

>400

Power supply

24V DC (12 - 30V DC) max 40mA



27.2.2. The way of installing inside PUE C41H

These modules are intended to mount inside PUE C41H. They need to be
connected to the 10-pin J12 connector. For all configurations of AN, there
is a gland installed on the back wall of the housing. A 3-meter shielded
cables are led out via the gland. Wires should be free from insulation.


Installation procedure:

1. Unplug the scale from mains;
2. Unscrew and take off the back wall of the housing;
3. Install your module in J12 on the main board;

4. During installation turn your attention to plastic columns. They

should be placed one side in mounting holes in the main board
and the other side in the mounted module;

5. Led the PT0015 cable through one of the free glands;
6. Connect the PT0015 cable to J3 on the analogue module according

to the description below;

7. Connect the PT0015 cable shield to the housing

(screwed terminator, 4mm diameter);

8. The cable connect to the group of wires (unhook band clips

fastening the group of wires, lay the cable and hook the band clips).
Band clips of multiple usage;

9. Screw down the back wall.